RECORDERS
SBR-EY & SBR-EM SERIES
![]() |
SBR-EY100 FEATURES:Universal inputsInteractive setup Brushless DC servo motor |
SBR-EM100 FEATURES:Simple operationCompact and reliable No set-up configuration at field |
![]() |
|
GENERAL DESCRIPTION
<SBR-EY100/180>The chart recorder SBR-EY series covers a wide range of specifications with 13 models of 144 x 144mm DIN size SBR-EY100 series (1-pen, 2-pen, 3-pen, and 6 dot-matrix). The SBR-EY series offers universal input and versatile optional functions such as serial communication, mathematical computations, IC memory card slot, alarms, and remote control.
<SBR-EM100/180> The SBR-EM series is easy-to-use recorders with high reliability and accuracy. Analog scale plate for each channel is standard equipment. Input ranges and units on the scale plate are configured at the factory so that you can yse it by simply powering up.
|
||||
|
OPERATING SPECIFICATIONS Input Signals DC voltage (±20mV to ±20V range) RTD (Resistance temperature detector) DC current (Adding external shunt resistance [10Ω, 100Ω and 250Ω]) Contact or Voltage input (TTL level) for SBR-EY Series
Refer to measuring range code table (P.5) for input signals, measuring range and measuring range limits.
REFERENCE JUNCTION COMPENSATION ACCURACY (more than 0°C) TC (Thermocouple) Type R, S, B, W5Re/W26Re : ±1°C Type K, J, E, Tm N, PLII, L, U : ±0.5°C *PLII is only referred to dot model of SBR-EY Series
DISPLAY <Only for SBR-EY Series> Display and Status Indicators Measured data (channel number or tag name, alarm type, measured value, engineering units) and time. Bar Graph Display Measured value: (1% resolution) Left-referenced or center-zero bar graph Display (Selectable for each channel). Alarm : Indicates alarm setting or ocured point. Alarm Display : Displays alarm setting and alarm channel number (dot model) Display Type : Vacuum Fluorescent Display (VFD)5x7 dot matrix
<Only for SBR-EM Series> Display Type: LED (7 segments, 2 digits) Displayed Information Depending on status, the following information can be displayed: Record number (channel display for dot model), alarms, end-of paper Alarm and battery end-of-life alarm. Scale Plate Specified graduation Black character, kind and symbol with white background. |
POWER SOURCERated power voltage 100 to 240V AC Useable power voltage Ranges: 90 to 132V AC, 180 to 250V AC Reated power frequency: 50/60 Hz
INSULATION RESISTANCEBetween termnals and ground: 20MW or more (at 500V DC)
DIELECTRIC STRENGTH1000v AC for one minute between measured terminals and ground 1000V AC for one minute between contact output terminals nd ground 1500V AC for one minute between power terminals and ground
*Between each input teterminals (between measuring channels) 1000V AC (50/60Hz)for one minute (Except RTD input dot printing model as the “b” terminal is common.)
Memory Backup Lithium battery to protect setup parameters. Life : approx. 10 years (at 23°C ± 2°C, 55% ± 10% RH, (for standard model) |
|||
|
FEATURES: |
||||
|
<SBR-EY100/180> Universal Inputs Interactive Setup |
<SBR-EM100/180> Simple Operations Compact and reliable |
|||
|
Brushless DC servo motor No set-up configuration at field
¶ HIGH RELIABILITY IN A COMPACT DESIGN ¶ SIMPLIFIED OPERATION CHOICE OF RECORDING STYLES
|
||||
![]()
Send
E-mail message
Fax Your Orders To: 1-800 358-7711
Direct Order Toll Free Line: 1-888 694-2129
!Canada